| Availability: | |
|---|---|
| | |
The SDM-AVF96D is a single-phase digital panel meter supplied with a matched CT-60 current transformer for current measurement from 1–60 A. It displays AC current, voltage and frequency on three digital display rows. The fixed CT ratio requires no user setting, simplifying installation and commissioning.
SDM-AVF96D
Samwha-dsp
6977363270989
The SAMWHA-DSP SDM-AVF96D measures single-phase AC current, voltage and frequency. Supplied with a matched CT-60 current transformer, it provides current measurement from 1–60 A.
The meter and CT use a fixed ratio, so users do not need to enter a CT primary-current value before operation. Its three-row digital display provides a clear view of the three measured parameters.
Measures single-phase AC current, voltage and frequency.
Supplied with a matched CT-60 current transformer.
Current measurement range: 1–60 A.
Fixed CT ratio with no user setting required.
Three-row display with three digits per row.
AC voltage measurement range: 10–500 V.
96 × 96 mm panel format.
Plug-in terminal connections.
The SDM-AVF96D is designed specifically for use with its matched CT-60. The CT ratio is fixed at the factory, eliminating the CT ratio setting step during commissioning.
Use the specified CT-60 with this model. Do not substitute a conventional 5 A secondary-output CT or a different CT model unless compatibility has been confirmed by the manufacturer.
| Parameter | Specification |
|---|---|
| Model | SDM-AVF96D |
| Measured parameters | Single-phase AC current, voltage and frequency |
| Matched current transformer | CT-60, included |
| Current measurement range | 1–60 A |
| CT ratio | Fixed; no user setting required |
| Voltage measurement range | 10–500 V AC |
| Auxiliary power supply | 150–240 V AC, 50/60 Hz |
| Power consumption | < 4 VA |
| Display | Three rows of three digits; 14 mm digit height |
| Panel format | 96 × 96 mm |
| Operating temperature | -20 to +55 °C |
| Connection | Plug-in terminals |
| Mounting | Panel mounting |
Single-phase distribution boards.
Electrical control cabinets.
Equipment panels requiring local current, voltage and frequency monitoring.
AC circuits requiring current measurement within the 1–60 A range.
Install the meter in the panel and connect the auxiliary supply, voltage measurement inputs and matched CT-60 according to the model-specific wiring diagram.
No CT ratio setting is required. Refer to the user manual for wiring and installation instructions.
Yes. The SDM-AVF96D is supplied with its matched CT-60 current transformer.
The current measurement range is 1–60 A when used with the specified CT-60.
No. The SDM-AVF96D uses a fixed CT ratio and requires no CT ratio setting.
The SDM-AVF96D is designed for its matched CT-60. For an adjustable-ratio solution using a conventional CT with a 5 A secondary output, select the SDM-AVF96.
No. Current is measured through the external matched CT-60. The measured load current does not pass directly through the meter's current input terminals.