SDM-AVF96
Samwha-dsp
6977363270989
The SAMWHA-DSP SDM-AVF96 combines AC current, voltage and frequency measurement in one panel-mounted instrument. Its three-row digital display allows operators to view all three electrical parameters at a glance.
Designed for electrical distribution boards and control cabinets, the SDM-AVF96 provides local monitoring of single-phase AC circuits.
Measures single-phase AC current, voltage and frequency.
Three-row display with three digits per row.
External current transformer input with a rated secondary current of 5 A.
Adjustable CT ratio for different primary-current ratings.
AC voltage measurement range of 10–500 V.
96 × 96 mm panel format.
Front-panel buttons for CT setting.
Plug-in terminal connections.
The SDM-AVF96 is designed for use with an external current transformer with a 5 A secondary output. Set the CT primary-current value through the front-panel menu to match the installed transformer.
For example, when using a 100/5 A CT, set the CT primary-current value to 100 A. The meter then displays the corresponding primary current.
The current measurement range depends on the selected CT and the meter's input specifications.
| Parameter | Specification |
|---|---|
| Model | SDM-AVF96 |
| Measured parameters | Single-phase AC current, voltage and frequency |
| Panel format | 96 × 96 mm |
| Auxiliary power supply | 150–240 V AC, 50/60 Hz |
| Power consumption | < 4 VA |
| Voltage measurement range | 10–500 V AC |
| Current input | External CT with 5 A secondary output |
| CT ratio setting range | 10/5 A to 9995/5 A |
| Display | Three rows of three digits; 14 mm digit height |
| Operating temperature | -20 to +55 °C |
| Connection | Plug-in terminals |
| Mounting | Panel mounting |
Single-phase distribution boards.
Electrical control cabinets.
Equipment panels requiring local current, voltage and frequency indication.
Replacement of separate ammeters, voltmeters and frequency meters.
Follow the wiring diagram for the SDM-AVF96 and use a CT compatible with its 5 A secondary-current input. Before normal operation, set the CT primary-current value to match the transformer nameplate.
Refer to the user manual for terminal connections and operating instructions.
It measures single-phase AC current, voltage and frequency.
Yes. When an external CT is used, its primary-current value must be entered through the front-panel menu.
Use an external CT with a 5 A secondary output and a primary-current rating suitable for the application.
The SDM-AVF96 allows the CT ratio to be set. The SDM-AVF96D, SDM-AVF109D and SDM-AVF209D use their specified matched CTs and do not require CT ratio setting.