Digital Smart Power
SDM-AVF209 Single-Phase Digital Multimeter with CT-300

loading

SDM-AVF209 Single-Phase Digital Multimeter with CT-300 SDM-AVF209 Single-Phase Digital Multimeter with CT-300

loading

SDM-AVF209 Single-Phase Digital Multimeter with CT-300

Availability:

The SDM-AVF209 is a single-phase digital panel meter supplied with a matched CT-300 current transformer for current measurement from 10–250 A. It displays AC current, voltage and frequency on three digital display rows. The factory-fixed CT ratio requires no user setting, simplifying installation and commissioning.

  • SDM-AVF209

  • Samwha-dsp

  • 6977363270989

Product Description

Single-Phase Current, Voltage and Frequency Monitoring

The SAMWHA-DSP SDM-AVF209 combines single-phase AC current, voltage and frequency measurement in one panel-mounted instrument. Supplied with a matched CT-300 current transformer, it provides current measurement from 10–250 A.

The three-row digital display allows operators to view all three measured parameters at a glance. Its fixed CT ratio eliminates the need to configure a CT primary-current value during commissioning.

Main Features

  • Measures single-phase AC current, voltage and frequency.

  • Current measurement range: 10–250 A.

  • Supplied with a matched CT-300 current transformer.

  • Factory-fixed CT ratio with no user setting required.

  • Three-row display with three digits per row.

  • AC voltage measurement range: 10–500 V.

  • 96 × 96 mm panel format.

  • Plug-in terminal connections.

Matched CT-300 for 10–250 A Measurement

The SDM-AVF209 is designed for use with its specified CT-300. The meter and current transformer form a fixed-ratio combination, so users do not need to enter a CT ratio before operation.

CT-300 identifies the matched current transformer. The specified current measurement range of the SDM-AVF209 combination is 10–250 A.

Use the supplied matched CT. Do not substitute a conventional 5 A secondary-output CT or another CT model unless compatibility has been confirmed by the manufacturer.

Technical Specifications

ParameterSpecification
ModelSDM-AVF209
Measured parametersSingle-phase AC current, voltage and frequency
Matched current transformerCT-300, included
Current measurement range10–250 A
CT ratioFixed; no user setting required
Voltage measurement range10–500 V AC
Auxiliary power supply150–240 V AC, 50/60 Hz
Power consumption< 4 VA
DisplayThree rows of three digits; 14 mm digit height
Panel format96 × 96 mm
Operating temperature-20 to +55 °C
ConnectionPlug-in terminals
MountingPanel mounting

Typical Applications

  • Single-phase distribution boards.

  • Electrical control cabinets.

  • Equipment panels requiring local current, voltage and frequency indication.

  • AC circuits requiring current monitoring within the 10–250 A range.

Installation and Commissioning

Install the meter in the panel and connect the auxiliary supply, voltage measurement inputs and matched CT-300 according to the model-specific wiring diagram.

Current is measured through the external CT. The measured load current does not pass directly through the meter's current input terminals.

No CT ratio setting is required. Refer to the user manual for terminal connections and installation instructions.

Frequently Asked Questions

What is the current measurement range?

The SDM-AVF209 measures current from 10–250 A when used with its specified CT-300.

Is a current transformer included?

Yes. The meter is supplied with a matched CT-300 current transformer.

Does CT-300 mean the meter measures up to 300 A?

No. CT-300 is the matched current transformer model. The specified measurement range of this meter and CT combination is 10–250 A.

Do I need to set the CT ratio?

No. The CT ratio is fixed at the factory and requires no user setting.

How does it differ from the SDM-AVF109?

The SDM-AVF209 uses CT-300 for 10–250 A measurement. The SDM-AVF109 uses CT-120 for 10–100 A measurement. Both use fixed CT ratios and require no CT ratio setup.

Which model supports an adjustable CT ratio?

The SDM-AVF96 supports an adjustable CT ratio for use with an external current transformer having a 5 A secondary output.


User Manual
Previous: 
Next: 
Dongfeng Industrial Zone Yueqing, Zhejiang, 325604, P.R.China
Phone: +86-577-57171337 Fax: +86-577-57171336
COPYRIGHT © 2019 Hannuo Electric ALL RIGHTS RESERVED